TNH60-63 high breaking miniature circuit breaker has the features of structure advanced, performance reliable,
breaking capacity high, appearance elegant and its shell and parts are made of material with impact resistance,
strong flame-retardant feature.
It is suitable to power system of 50or 60 frequency ,Ue 400V and below, Ui 63A and below.
It is mainly applied at office building, residence, for lighting , power distribution and overload and short circuit
protection of equipment. Normally, it also can be used as the not frequent transfer of power system. It conforms
to the standards IEC60898and GB10963.1.
Type |
TNH60-63 |
Pole |
1P |
2P, 3P, 4P |
Rated current (A) |
6, 10, 16, 20, 25, 32, 40, 50, 63 |
Rated voltage (V) |
230 |
400 |
Ambient temperature |
-5 o C~+40 o C |
Type of instantaneous release |
C |
D |
C |
D |
Rated short circuit breaking capacity Icn(kA) |
1-32A: 6 50-63A: 4 |
4 |
1-32A: 6 50-63A: 4 |
4 |
Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
Note |
30±2 o C |
Cold position |
1.13In |
t≥1h |
Non-release |
- |
Carried out immediatelyafter previous test |
1.45In |
t < 1h |
Release |
- |
Cold position |
2.55In |
1s < t< 60s(In≥32A) |
Release |
Current smoothly rises tospecified value within 5s |
Cold position |
2.55In |
1s < t < 120s(In>32A) |
Release |
-5~+40 o C |
Cold position |
3In |
t≥0.1s |
Non-release |
Type B |
Cold position |
5In |
t < 0.1s |
Release |
Type B |
Cold position |
5In |
t≥0.1s |
Non-release |
Type C |
Cold position |
10In |
t < 0.1s |
Release |
Type C |
Cold position |
10In |
t≥0.1s |
Non-release |
Type D |
Cold position |
20In |
t < 0.1s |
Release |
Type D |
Rated current(A) |
Norminal cross section of wire mm 2 |
1-6A |
1 |
10A |
1.5 |
16,20A |
2.5 |
25A |
4 |
32A |
6 |
40,50A |
10 |
63A |
16 |
TYNEHAM. We also welcome OEM.